Status reports and indicators are untrustworthy, UPS battery edition
A lot of things these days can report useful information about their status and health. Or at least their theoretical status and health. As we've seen, things like server BMCs may be reporting outdated hardware inventories. Today I got another vivid illustration of that, when Toronto had what you could call a significant weather event with some power flickers in my area, and I made an unhappy discovery about my home UPS:
TIL that my home UPS has recently become a home power bar or maybe a home line conditioner, despite claiming that its battery is fine. Well, itβs six years old, but on the other hand it worked in June.
(Specifically it worked on June 1st early in the morning, for a few seconds, and before that on May 23rd.)
This particular UPS is a bit over six years old, and has been periodically useful during fortunately infrequent brief power outages. But this time, when the power flickered briefly everything connected to the UPS powered off, which is the reverse of what I'd like. After a couple more power flickers, the UPS stayed off for long enough that I disconnected everything and switched back to my pre-UPS power bar.
I have monitoring of the UPS set up on my home desktop, and all during the power events both it and the UPS's front panel display claimed that the UPS had 100% battery, the battery was at 24 volts, and so on (even after a power flicker had caused the UPS and everything attached to it to shut off, then power came back and everything turned on). But once I disconnected everything from the UPS and was able to get the UPS to do a proper self test, it abruptly switched to reporting 6% battery charge, which is a much more realistic number for something that fell over more or less the moment it needed to supply battery power (and there are some indications that even that's misleading; for example the nominal charge level will drop from 20% to 5% in a few seconds even with nothing connected to the UPS).
I knew that battery charge reporting was somewhat unreliable for Li-ion batteries, but I don't think I've seen this before in regular batteries and our rack UPSes at work have always been reasonably good about reporting that their batteries needed replacement. Unreliable reporting of battery status matters for more than surprising me when the power went out; initially it made me think that the entire UPS unit needed to be replaced, rather than just the batteries (probably) being worn out.
(I was willing to believe that the batteries were dead, but a UPS that firmly reported dead batteries as being completely good seemed like a UPS that might have additional problems that had degraded its ability to work right in general.)
PS: In the long run, I should plan to periodically test that the UPS can support the load when line power goes off, either through its own self test or by manually switching it away from line power with a front panel switch. Obviously I'd better do this at a time when I can afford to have my desktop abruptly lose power.
Sidebar: Did the UPS make things worse?
None of the power flickers lasted long enough to cause the usual run of kitchen appliances to reset their clocks, and there were a few more power flickers after I'd moved everything to the power bar and nothing rebooted. Modern desktop PSUs apparently normally have a hold-up time of 16 milliseconds or more (it's apparently part of the ATX specification, although I haven't looked to be sure), which is the length of time the PSU should keep supplying power after the line power goes away. So these power flickers seem to have been very brief, but apparently they were still long enough that the UPS tried to switch to battery power (and then had battery power fall over).
If the UPS had not detected power loss and tried to switch, it seems possible that everything would have survived fine. On the other hand, I wouldn't know that the UPS had problems.
(The UPS definitely made things better back in June and May.)